Compressor Envelope: Summer and Winter Operating Points

Is the compressor inside its envelope? HVACinOne solves the cycle and draws both seasonal operating points on the compressor's own envelope.

0:48

Is the compressor inside its operating envelope in summer and in winter? A capacity and COP line on a datasheet does not say where the compressor actually runs. To check the envelope by hand, you read the evaporating and condensing temperatures off the cycle. Then you plot them on the compressor maker's chart, once for summer and once for winter. In a heat pump the two seasons can sit far apart.

HVACinOne solves the refrigerant cycle of the unit for each season. It then draws the envelope of the selected compressor from its envelope data, for the same refrigerant and frequency, and puts the solved operating points on it: the summer point in red, the winter point in blue. Both points stay on one chart. The solved values of every other component, such as the condenser and the fans, are kept on the unit's own schema, so the whole cycle can be checked in one place.

Take a rooftop heat pump at 4500 m³/h. The envelope covers evaporating temperatures from −30 °C to 25 °C and condensing temperatures from 20 °C to 68.3 °C, at 10 K superheat. In summer (35 °C outdoor, return 27 °C / 50 %) the cycle solves to Te 6.4 °C and Tc 49.6 °C, with 26.9 kW cooling. In winter (5 °C outdoor, return 25 °C / 28 %) the outdoor coil becomes the evaporator: Te −3.7 °C, Tc 48.3 °C, 26.5 kW heating. In this example both points are inside the envelope.

This helps selection and product engineers for rooftops and heat pumps check the compressor's operating limits in every season, without plotting points by hand.