How much capacity does a CRAC lose with long field piping? A CRAC is selected as a unit. But on site the condensing unit often sits on the roof, tens of metres of pipe away. The suction gas loses pressure on its way up, so the compressor sees a lower saturated suction temperature than the evaporator. The pipes also hold refrigerant. Does the selected capacity still hold?
In HVACinOne the field piping between the condensing unit and the CRAC is entered for each calculation: horizontal length, vertical distance (plus sign: the unit is above), gas line and liquid line. It is not added afterwards. The pipe pressure drop, from straight pipe and static head, is solved inside the cycle at every iteration. The coil temperatures shift with the line drop, and the refrigerant held in the field pipes is added to the charge. Bends and fittings are not included.
Take one CRAC with R410A, 10000 m³/h, return air 27 °C / 50 % and outdoor 35 °C, with a correctly sized 1 3/8 in gas line and a 5/8 in liquid line. With 50 m horizontal and the unit 15 m above, the suction line loses 0.50 bar: 7.8 °C saturated at the evaporator, 6.1 °C at the compressor. The liquid line runs down and gains 0.08 bar, and the field pipes hold 11.31 kg. Against 5 m on the same level, capacity drops from 47.63 kW to 45.83 kW (−3.8 %), and the pipes hold 10.4 kg more refrigerant. Both cases are calculations, not measurements.
This helps engineers who design computer rooms and data centres check the real pipe run during selection, not after installation. They see the capacity loss and the extra refrigerant charge before the unit is ordered.