What is the real heating capacity of a heat pump coil? The supply coil is usually selected for cooling. There it is the evaporator, and the refrigerant runs against the air: counter flow. In heating, the 4-way valve flips. Every refrigerant line in the circuit runs the other way, but the air does not. Hot gas now enters on the air-entering side, so the same coil works as a condenser in parallel flow. A heating capacity rated as counter flow assumes a flow the coil does not run.
For coils calculated with its built-in coil engine, HVACinOne solves the heating case in parallel flow, the direction the coil actually runs. Cooling stays in counter flow. Both modes use the same coil geometry and the same calculation, so the two results can be compared directly.
Take one coil with 24 tubes × 4 rows × 1000 mm, 12 circuits and 5000 m³/h. In cooling at 7 °C evaporating, it gives 25.51 kW and cools the air from 27.0 °C to 14.8 °C. In heating the inputs are 45 °C condensing, 25 K desuperheat, 5 K subcooling, R410A and 20.0 °C entering air. Rated as counter flow, the coil gives 29.36 kW and 37.4 °C supply air. Solved in parallel flow, it gives 26.58 kW and 35.8 °C: −9.5 % capacity and −1.6 K supply air in this example. The heating answer is 26.6 kW, not 29.4.
This helps selection engineers of heat pump units check the heating mode before they finalise the coil, with the same inputs for both flow arrangements. The heating capacity they quote is the one the coil can deliver in the flow it really runs.