← All videos Refrigeration cycle

Inverter Compressor: Enter the Load in kW, Not Hz

The client gives the load in kW, the inverter wants Hz. HVACinOne takes the kW and finds the stage and the frequency itself.

0:53

The client gives a load in kW, but an inverter compressor is entered in Hz. In a frequency based calculation every selected compressor runs. So the engineer guesses a frequency, calculates, and tries again. With an on/off compressor in the same circuit, a small load may never be reached at all.

HVACinOne also offers a capacity based calculation. You enter the demand in kW and a tolerance (±3 % by default). The program orders the stages from small to large: the inverter is always on, the on/off compressors are on or off. It checks each stage once at 120 Hz, takes the first stage that reaches the demand, and searches the inverter frequency on the real refrigerant cycle, in whole Hz. If even the largest stage is short at the highest frequency, it says so.

Take one rooftop circuit with an inverter scroll (25–120 Hz) and an on/off scroll, at 6000 m³/h, 35 °C outdoor and 27 °C / 50 % return air. With both compressors running, the unit never goes below 17.65 kW, even at 25 Hz: 47 % more than a 12 kW load. The capacity based calculation keeps the on/off compressor off and finds 47 Hz: 11.83 kW, −1.4 %, inside the tolerance. At 26 kW it runs both compressors at 92 Hz (26.76 kW). At 40 kW it reaches 30.05 kW at 120 Hz and warns that the demand is not met.

This helps selection engineers of inverter units check part-load operation without trying frequencies by hand. Frequency based calculation stays available when you want to set the Hz yourself.