← All videos Refrigeration cycle

Reheat Coil After Dehumidification: Water Side Solved

Same coil, same air, two answers. HVACinOne solves the reheat coil's water flow and return water at the target leaving air temperature.

0:42

After a dehumidifying evaporator, the air is too cold to supply, so a reheat coil warms it again. The air-side duty is easy to estimate by hand. The water side is not. At the target, how much water does the coil need, and what temperature comes back? A coil quoted at its rating answers neither question.

In HVACinOne the heater control type sets the operating point of the reheat coil. With Capacity, the coil runs at its rating with the entered water temperatures. With Leaving air temperature, the water inlet stays fixed and HVACinOne searches the water flow until the air leaves within ±0.1 K of the target. The return water is a result, not an input. With Water flow, you give the flow and get the capacity, the leaving air and the return temperature.

Take a heat pump unit with a heat recovery rotor in summer: 1500 m³/h, 100 % outdoor air at 35 °C / 40 %. The evaporator dries the air to 17.6 °C at 88 % RH. Its duty is 8.8 kW, and 3.6 kW of it is latent. At its rating (water 35/30 °C, 619 kg/h) the reheat coil gives 3.6 kW and 25.1 °C, above the 22 °C target. Solved at the 22 °C target, the same coil gives 2.1 kW. The water flow drops to 211 kg/h, 34 % of the rating flow, and the return water is 26.4 °C. With a fixed 400 kg/h it gives 3.1 kW, 24.1 °C air and 28.3 °C return.

This helps selection engineers working on heat pump units and air handling units with dehumidification. They see the real water flow and return temperature at the design point, not the coil's rating.

Want to see this with your own products?

We set up HVACinOne with your unit data and show the same calculation on your range.

More videos