Is the Eurovent energy class of an air handling unit fixed, or does it depend on where the unit is installed? It is often quoted as a property of the AHU alone. Under the Eurovent AHU energy efficiency method it is not. In winter the method compares fan power with a reference that includes a heat recovery penalty, and that penalty grows as the winter design temperature of the site falls. The colder the climate, the more each missing point of heat recovery efficiency costs.
HVACinOne calculates the Eurovent energy class (2026 rules) inside every AHU selection, for unit types set up as Eurovent certified. Face velocity, fan static pressure, heat recovery efficiency and pressure drop, and fan input power all come from the same calculation. The winter design temperature comes from the project city or from the value the engineer enters. The result gives the class, the subgroup and the fan power ratio f.
Take an AHU with plate heat recovery at 6000 m³/h, 100 % outdoor air, 250 Pa external pressure on each side and 78 % heat recovery efficiency. In Istanbul (0.2 °C) the fans draw 2.82 kW against a 3.28 kW reference: f = 0.86, class A+. In Erzurum (−26.1 °C) the heat recovery penalty at A+ rises from 40 Pa to 132 Pa on each side. The ratio reaches 1.04, and the same unit drops to class A.
Selection and sales engineers can quote the energy class for the site where the unit will actually run, and see early when heat recovery needs more attention. Calculated results do not constitute Eurovent certification.