What are the FCEER and the Eurovent class of a fan coil unit before it goes to the lab? A new or changed fan coil configuration has no certified value yet, so the class is usually known only after the lab test. Catalog values do not help either, because they cannot show what a configuration change does to the fan.
HVACinOne calculates the FCEER inside the selection, with the coil and fan actually selected. The unit is solved at the Eurovent standard condition: room air 27 / 19 °C, chilled water 7 / 12 °C, 100 % room air and 0 Pa external static pressure for a non-ducted unit. It runs at three speeds, which are the unit's own minimum, standard and maximum air flow. Fan power is taken off the gross capacity. Then net cooling and fan power are weighted 65 / 30 / 5 % over the three speeds. The weights and the class table come from Eurovent ECP-1A FCU.
In this example, a 2-pipe changeover fan coil runs at 700 / 1000 / 1300 m³/h. Gross cooling is 6.45 / 8.91 / 11.22 kW and fan power is 95 / 133 / 169 W. Weighted net cooling is 7.32 kW and weighted fan power is 110 W, so FCEER is 66.5, class D. As a 4-pipe unit, the same fan and the same cooling coil get a second coil. It gives no heat in summer, but the air still passes it. Fan power rises to 116 W and FCEER drops to 62.8, which is 5.6 % lower. The class stays D in both cases.
This helps fan coil product and selection engineers compare configurations before they go to the lab. Calculated results do not constitute Eurovent certification.