Which compressor option gives a rooftop unit the better SEER, SCOP and Eurovent seasonal class? Most people compare rooftop units at the full-load point, the EER at 35 °C. But a rooftop runs at full load only a few hours a year. The Eurovent seasonal rating looks at the whole season, so the part-load points decide the class.
HVACinOne builds the EN 14825 load line from the design point. It solves every point with the selected compressor, both coils and the fans. A fixed-speed compressor has too much capacity at part load, so it cycles on and off. With an inverter, HVACinOne searches the frequency at every point, so the capacity follows the load. The four cooling points give the SEER. The SEER becomes the seasonal efficiency ηs,c, and the class follows from it. Net values are used, with fan power corrected per EN 14511-3. The user enters no test data.
Take one rooftop at 4500 m³/h, 100 Pa external pressure and a 25.9 kW design load, with the same coils and fans for every option. At 20 °C the load falls to 21 %, or 5.5 kW. The fixed-speed compressor still gives 28.9 kW there, while the inverter drops to 25 Hz. The EER at 35 °C is 2.90, 2.92 and 2.89 for one fixed compressor, two fixed compressors and the inverter. But SEER is 3.08, 4.15 and 4.18. SCOP is 2.76, 3.33 and 3.23. So in this example the single compressor gets class C / D, and both other options get B / B. The tandem leads on SCOP.
This helps rooftop product and selection engineers compare compressor options on the same load line, with one click per option. Calculated results do not constitute Eurovent certification.