Custom Fan Selection from Catalog Curves

Enter the catalog points once. HVACinOne fits each curve and solves fan speed and power between the measured curves.

0:42

How do you select a fan from catalog curves only? Many fans come without a selection program. The engineer has only the printed catalog curves. So the duty point is read off the chart, and the fan is sized on the next curve up, often the full-speed curve. That overstates both the fan speed and the power input.

In HVACinOne you enter the catalog points of the fan once: air flow, static pressure and power for each speed curve, at least 5 points per curve. One click fits a polynomial to each curve. The degree is chosen by the user, from 1 to 6, and the coefficients are stored with the fan. The selection screen then draws the curves and checks every custom fan against the duty point. When the duty point sits between two measured curves, speed and power are interpolated at the duty air flow. The same polynomial runs on the selection screen, in the unit functions and in the device curve.

Take a custom 560 mm EC fan with 34 catalog points on 3 curves: 836, 1292 and 1520 rpm. A cubic curve is fitted to each speed. The duty point is 10000 m³/h at 500 Pa. Of 34 custom fans checked, 3 reach it. At 10000 m³/h the operating curve gives 380 Pa at 1292 rpm and 1.53 kW. The full-speed curve gives 636 Pa at 1520 rpm and 2.63 kW. Solved at the duty point, the fan runs at 1399 rpm with 2.05 kW, a static efficiency of 67.9 % and SFP 0.74. In this example, the power input is 22 % below the full-speed curve.

This helps unit designers and selection engineers who use custom or in-house fans without a vendor selection program.

Want to see this with your own products?

We set up HVACinOne with your unit data and show the same calculation on your range.

More videos