A building owner wants ventilation and heating on the existing ducts. Duct-mounted fan, filter, heat recovery and heater boxes fit in the duct, so size is no problem. But each box is sold on its own, with its own data. What do they do together? The fan must work against every box in the duct, and the supply air depends on the whole chain.
In the HVACinOne project module, the boxes chosen for each duct are assigned as accessories of one device and calculated together. Every box keeps its alternatives, picked per project. The result shows heat recovery efficiency, supply air temperature and humidity, and a fan duty that includes the pressure drop of every box. Each duct gets its own price and technical output: PDF datasheet, Excel or a project ZIP.
Take 5000 m³/h, 250 Pa external pressure, winter outdoor air at −5 °C / 90 % and extract air at 22 °C / 40 %. As single boxes: the F7 filter box has 54 Pa, the heat recovery box 78.9 %, the heater box 12.3 kW and the fan box 0.62 kW at 250 Pa. Three ducts get their own box sets. Duct A (supply and heating) needs 45.5 kW and supplies 20.2 °C. Duct B (heat recovery) supplies 18.0 °C. Duct C (heat recovery and heating) supplies 25.3 °C / 12 % with 12.3 kW and 1.93 kW fan input. In duct C the supply fan static pressure is 457 Pa: 250 + 137 + 54 + 11 + 5 Pa. The same fan as a single box sees only 250 Pa.
This helps R&D, engineering, product management and technical sales teams at HVAC manufacturers who sell duct-mounted boxes.