Does fan motor heat raise the supply air temperature? Datasheets often print the coil leaving temperature as the supply air temperature. But in many units the fan sits after the coil, and its motor is in the air stream. All of the fan input power ends up as heat in the supply air. So the air that leaves the unit is warmer than the air that leaves the coil.
HVACinOne adds this heat after the coil. It uses the input power of the selected fan and treats it as sensible heat: the temperature rises, the absolute humidity stays the same. The temperature rise follows ΔT = P / (ṁ·cp). The coil load does not change; the supply temperature does. Fan heat is applied in every unit function, except Eurovent certification functions and condensing units.
Take a supply air unit in summer with filter, cooling coil and fan: 5000 m³/h, 100 % outdoor air at 32 °C / 41 %, chilled water 7/12 °C and 250 Pa external pressure. The cooling coil takes the air from 32.0 °C to 13.6 °C with 44.8 kW. The fan after the coil uses 0.87 kW. At 5000 m³/h this warms the air by 0.54 K. With fan heat ignored, the supply air is 13.6 °C. With fan heat added, it is 14.1 °C, while the coil leaving air stays at 13.6 °C. A typical rise is 0.4–0.6 K.
This helps selection engineers report the temperature the unit really delivers, together with the selected fan's power, instead of the coil leaving temperature.