How do you move a rooftop unit from R410A to R32? F-gas rules keep changing. Under EU 2024/573, each step means redesigning units for a new refrigerant: new parts and new checks. Done by hand, this means re-selecting the unit and checking every part again. It is usually long and tiring.
In HVACinOne, the unit keeps its casing, fans and coil geometry. You change only what the new refrigerant needs, in three steps. First, select a compressor made for the new refrigerant. Second, rate the coils with the new refrigerant, and resize them only if the refrigerant needs it. Third, calculate. One run solves the whole cycle again, and the result shows at once what changed. The calculation took 9 s in our test.
Take one rooftop with one circuit, at 6000 m³/h and 35 °C outdoor. Here the coils keep their geometry and only the compressor model changes. On R410A, capacity is 24.12 kW, compressor power is 6.23 kW and compressor EER is 3.87. The estimated refrigerant charge is 5.45 kg. On R32, capacity is 24.15 kW, compressor power is 6.05 kW and compressor EER is 3.99. The estimated charge drops to 4.40 kg. So in this example, R32 needs 19 % less refrigerant at the same capacity. For the next refrigerant, the workflow is the same: change the parts, calculate, compare. What changes depends on the refrigerant.
This helps R&D, product and technical sales teams who must move product lines to new refrigerants. They redesign and check each unit in one tool, with the same calculation they already use for selection.